EXPLOSION ISOLATION SYSTEM – HRD BARRIER





                                                                            HRD barriers are characterized by extremely fast discharge of an extinguishing agent into pipes
                                                                            connecting pieces of technological equipment. Explosion pressure propagates through the pipes
                                                                            first during an explosion followed by a flame front. Both of these quantity can be detected by
                                                                            special detectors – both optical and pressure that were developed for the purpose.


                                                                                                                  ADVANTAGES:
                                                                              HRD barrier is suitable for prevention   • High reaction speed of the system from
                                                                              of explosion propagation in pipes of     detection to extinguishing
                                                                              filters, reservoirs, mills, crushers,   • Independent archiving of detector data
                                                                              separators, cyclone dryers and      • Variability of detector, control unit and
                                                                                                                    container unit use
                                                                              other devices with danger of dust   • High quality components
                                                                              explosions.                         • Customization according to customer
                                                                                                                    quality wishes
                                                                                                                  • Use in inside and outside areas
                                                                                                                  • High reliability of the system

                                                                              MEETS      2014/34/EU
                                                                                          ATEX 114




     DIAGRAM OF HRD BARRIER INSTALATION ON A PIPE
                                                                            The detectors relate a signal to a control
                                                                            unit that activates HRD container units. The
                                                                            bottles are equipped by fast-opening valves
                                                                            capable to immediately release extinguishing
                                                                            agent to the protected space, and create very
                                                                            effective extinguishing agent barrier.
                                    6
             5                                                    2
                            1                          5



                                                                            1. Explosion detector
                                                                 4          2. Fan
                                                                            3. Rotary valve
                                                                            4. Control unit
                                     3                                      5. HRD container unit
                                                                            6. Filter


                                                                                                                                                      15